Back
Where to buy Contact us
PHP-LABCMFTD01-MSL

MULTIFIX® 60 , D02 Vertical Switch Fuse Disconnector 63A, 400VAC, Triple Pole

Approvals & Standards
IEC/EN 60 947-3
For D01- and D02-fuse links and D0-push-in gauge piece in accordance with IEC/EN 60 269-3, VDE 0636-3

MULTIFIX® 60 is a system for energy distribution comprising a variety of modular combinable components. The energy distribution is carried out via copper bus bars in a 60 mm bus bar system up to 630 A, 400 V AC, 500 V AC, 690 V AC, 45–62 Hz. Short circuit withstand tested to VDE 0660 part 500 and IEC 60439-1. MULTIFIX® 60 is suitable for triple pole, quadruple pole and quintuple pole applications. The components of the MULTIFIX® 60 system are mounted directly without drilling. This method offers high flexibility for extension and alteration of existing installations -> reduced installation time. D02-vertical switch fuse disconnector 63A, 400VAC, triple pole is installed on to 60 mm bus bar directly by snap in mode and automatic interlocking. It is designed for bus bars with a width of 12 to 30 mm and a thickness of 5 to 10 mm. Width of switch is only 27 mm which allows space saving, system compatible installation. The Plug technique to EN 50110-1 allows installation without screw caps.

MULTIFIX® 60 is a system for energy distribution comprising a variety of modular combinable components. The energy distribution is carried out via copper bus bars in a 60 mm bus bar system up to 630 A, 400 V AC, 500 V AC, 690 V AC, 45–62 Hz. Short circuit withstand tested to VDE 0660 part 500 and IEC 60439-1. MULTIFIX® 60 is suitable for triple pole, quadruple pole and quintuple pole applications. The components of the MULTIFIX® 60 system are mounted directly without drilling. This method offers high flexibility for extension and alteration of existing installations -> reduced installation time. D02-vertical switch fuse disconnector 63A, 400VAC, triple pole is installed on to 60 mm bus bar directly by snap in mode and automatic interlocking. It is designed for bus bars with a width of 12 to 30 mm and a thickness of 5 to 10 mm. Width of switch is only 27 mm which allows space saving, system compatible installation. The Plug technique to EN 50110-1 allows installation without screw caps.

Key features & benefits

  • For bus bars with width 12 - 30mm and thickness 5 - 10mm

  • For direct installation without drilling on to 60mm bus bar systems

  • Ease of installation - snap in mode and automatic interlocking

  • Blinking indicator for indication of operation of fuse link

  • Plug technique to EN 50110-1 - installlation with screw caps

  • Indication of switch contact

  • Padlocking and sealing facility

  • Special adapter ring for the use of D01-fuse links (included in delivery)

  • For D01- and D02-fuse links and D0-cartridge ring adapter inserts in accordance with IEC/EN 60269-3, VDE 0636-3

Applications

  • Panel board builders

  • Control system engineering

  • Industrial plants

  • Heating & air conditioning systems

Technical Specifications
Short Circuit Current Rating (SCCR) 50 kA@Ue = AC 400 V; Ie = 63 A
CE Conformity Yes
Reach Compliant Yes
Degree of Protection (IP) IP20

Reference Finder

4 references in this series

Scroll

Item number Fuse size Sort ascending Number of poles Product weight
M1006399 - 1.002.602 See product
D02 3-Pole 0.35kg
P1006401 - 1.002.603 See product
D02 3-Pole+N 0.44kg
R1026620 - 1.002.604 See product
D02 3-Pole 0.35kg
S1026621 - 1.002.605 See product
D02 3-Pole+N 0.44kg
Back to top