D1023273 - 1.000.096
NH fuse-switch disconnector MULTIVERT® Size 4a 1600A 3x1-Pole switching Screw top terminal M12
MULTIVERT® NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements. MULTIVERT® 1250A are for installation on to 185mm bus bar systems. MULTIVERT® 1250A are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 4a: 1250A. MULTIVERT® offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance.
NH fuse-switch disconnector MULTIVERT® Size 4a 1600A 3x1-Pole switching Screw top terminal M12
MULTIVERT® NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements. MULTIVERT® 1250A are for installation on to 185mm bus bar systems. MULTIVERT® 1250A are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 4a: 1250A. MULTIVERT® offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance.
Datasheets
Compliances
Item number | D1023273 |
Catalogue No | 1.000.096 |
Description | NH fuse-switch disconnector MULTIVERT® Size 4a 1600A 3x1-Pole switching Screw top terminal M12 |
EAN/UPC Code | 9008567009673 |
Frequency (Hz) | 50 ... 60 Hz |
Rated voltage AC IEC | 690 V |
Ampere Rating | 1600 A |
Utilization Category | AC 21 B @ Ue = AC 400 V; Ie = 1600 A |
Switchability | coupure 3x1-pôle |
ROHS Compliant | Yes |
AC or DC | AC |
Short Circuit Current Rating (SCCR) | 31,5kA@Ue = AC 400 V; Ie = 1600 A |
Fuse Size | 4a |
Design Details | Screw top terminal |
Number of Poles | 3-Pole |
Degree of Pollution | 3 |
Rated Impulse Withstand Voltage | 8 kV |
Rated Insulation Voltage | 1000 V |
Rated SC Withstand | 32 kA / 1 s |
Max Power dissipation of Fuse Links Pn | 140 W |
Max Power dissipation of Solid Links Pn | 42 W |
Power Dissipation by Ith without Fuse-Links | 568 W |
Rated short circuit making capacity with solid links Icm | 68 kA |
Installation Mounting | Bus Bar Installation |
Product Width | 4.96 in |
Product Length | 10 in |
Product Height | 39.02 in |
Sell Pack Quantity | 1 EA |
Sell Pack Weight | 36.376 lb |
Sell Pack Width | 6.69 in |
Sell Pack Length | 43.31 in |
Sell Pack Height | 11.02 in |
Product group | IEC Fuse Switch Disconnectors |
Product Weight | 36.376 lb |
Conventional Free Air thermal Current With Fuse-Links Ith | 1600 A |
Conventional Free Air thermal Current - Solid Links | 1600 A |