A6D300/600R
Reducer Fuse A6D-R - Class RK1 - Time-Delay 600VAC 600VDC 300A Blade SmartSpot® Amp-Trap 2000®
Solid-state SmartSpot indicator Time-delay for motor starting and transformer inrush currents without nuisance opening 300kA interrupting rating, self-certified (UL witnessed test) Extremely current-limiting for low peak let-thru current Easy 2-to-1 selectivity for prevention of nuisance shut downs and "black outs" Rejection-style design prevents replacement errors (when used with recommended fuse blocks) High-visibility orange label gives instant recognition Reduced inventory by taking the place of Class RK5, K, and H fuses Metal embossed date and catalog number for easier traceability and lasting identification Fiberglass body provides dimensional stability in harsh industrial settings High-grade silica filler ensures fast arc quenching
Reducer Fuse A6D-R - Class RK1 - Time-Delay 600VAC 600VDC 300A Blade SmartSpot® Amp-Trap 2000®
Solid-state SmartSpot indicator Time-delay for motor starting and transformer inrush currents without nuisance opening 300kA interrupting rating, self-certified (UL witnessed test) Extremely current-limiting for low peak let-thru current Easy 2-to-1 selectivity for prevention of nuisance shut downs and "black outs" Rejection-style design prevents replacement errors (when used with recommended fuse blocks) High-visibility orange label gives instant recognition Reduced inventory by taking the place of Class RK5, K, and H fuses Metal embossed date and catalog number for easier traceability and lasting identification Fiberglass body provides dimensional stability in harsh industrial settings High-grade silica filler ensures fast arc quenching
Datasheets
pdf - 165.71 KB
Curves
pdf - 50.2 KB
Drawings
pdf - 121.02 KB
pdf - 121.02 KB
Item number | A6D300/600R |
Description | Reducer Fuse A6D-R - Class RK1 - Time-Delay 600VAC 600VDC 300A Blade SmartSpot® Amp-Trap 2000® |
EAN/UPC Code | 782001489465 |
Rated voltage AC UL | 600 V |
Rated voltage DC UL | 600 V |
Frequency (Hz) | 50/60 Hz |
Ampere Rating | 300 A |
ROHS Compliant | Yes |
AC or DC | AC/DC |
Fuse Class | Class RK1 |
Speed/Characteristic | Time Delay |
Mounting | Clip |
AC Max I.R./Breaking Capacity: I1 | 200 kA |
Indication System | Yes |
Indication System Type | SmartSpot® |
Connection/Terminal Material | Tin-Plated Copper |
Connection/Terminal Type | Blade |
Product Diameter | 3.12 in |
Product Length | 13.38 in |
Sell Pack Quantity | 1 EA |
Sell Pack Weight | 6.2 lb |
Sell Pack Width | 3.25 in |
Sell Pack Length | 13.75 in |
Sell Pack Height | 3.12 in |
Product group | Low Voltage UL/CSA Fuses |
Body/Insulating Material | PolyTube |
Product Weight | 5.9 lb |