BS88 Fusibles piliers d alimentation gG 415 VAC
The majority of existing street lighting networks are normally protected by a common Feeder Protection Device (FPD). FDP is based on a simple overcurrent unidirectional technique to protect against faults on the street lighting cables. The Mersen fuse technology ensures safety in street lighting applications by providing better coordination, immediate isolation and ensures fire safety through safe and correct fuse selection.
The Mersen range of Low Voltage Feeder Pillar Fuse Links are designed for the use with wedge type fuse carriers with fixing centres of 82mm and 92mm. There are primarily for use by Electricity Supply Industries in distribution pillars, open type substation boards, heavy duty service cut-outs and underground disconnecting boxes.
The majority of existing street lighting networks are normally protected by a common Feeder Protection Device (FPD). FDP is based on a simple overcurrent unidirectional technique to protect against faults on the street lighting cables. The Mersen fuse technology ensures safety in street lighting applications by providing better coordination, immediate isolation and ensures fire safety through safe and correct fuse selection.
The Mersen range of Low Voltage Feeder Pillar Fuse Links are designed for the use with wedge type fuse carriers with fixing centres of 82mm and 92mm. There are primarily for use by Electricity Supply Industries in distribution pillars, open type substation boards, heavy duty service cut-outs and underground disconnecting boxes.
Product data sheets
- DS-Feeder-Pillar-Fuse-gG-415-VAC-EN
pdf - 386.48 KB
Key features & benefits
Better coordination
Immediate isolation
Ensures fire safety
Applications
Feeder pillar for street lighting
Electricity Supply Industries in distribution pillars
Open type substation boards
Heavy duty service cut-outs
Underground disconnecting boxes
Technical Specifications
Voltage Range | 415 VAC |
Amperage Range | 20-630A |
Speed/Characteristic | gG |
CE Conformity | Yes |
Reference Finder
Scroll
Item number | Ampere rating | Fuse size | Clearing I2t At Rated Voltage | Indication System | Product weight |
---|---|---|---|---|---|
A1003904 - BJU42V063SA See product
|
63A | 130x36 | 18000A²s | No | 0.281kg |
B1003905 - BJU42V080SA See product
|
80A | 130x36 | 21000A²s | No | 0.281kg |
C1003906 - BJU42V100SA See product
|
100A | 130x36 | 37000A²s | No | 0.281kg |
D1003907 - BJU42V125SA See product
|
125A | 130x36 | 74700A²s | No | 0.281kg |
D1003930 - BJU42V400PB See product
|
400A | 110x42 | 720000A²s | No | 0.244kg |
E1003931 - BJU42V250SB See product
|
250A | 130x42 | 270000A²s | No | 0.316kg |
F1003932 - BJU42V315SB See product
|
315A | 130x42 | 472500A²s | No | 0.316kg |
F1003955 - BJU42V500SC See product
|
500A | 130x50 | 1359000A²s | No | 0.398kg |
G1003933 - BJU42V355SB See product
|
355A | 130x42 | 603300A²s | No | 0.316kg |
G1003956 - BJU42V560SD See product
|
560A | 130x74 | 2910000A²s | No | 0.706kg |