MFP Mersen Feeder Panel

Mersen Feeder Panel (MFP)

Designed to meet requirements defined by the National Electrical Code® (NEC) to protect critical power operations and distribute power to general purpose operations
Designed to meet requirements defined by the National Electrical Code® (NEC) to protect critical power operations and distribute power to general purpose operations
  • For panels with circuits requiring ratings greater than 100A, Mersen offers a 38” wide panel with fusible switches for over-current protection. The Mersen Feeder Panel (MFP) is designed to meet requirements defined by the National Electrical Code® (NEC) to protect critical power operations and distribute power to general purpose operations. The MFP can integrate Mersen’s Critical Power Panel (CPP) as the sub-panel, capable of distributing power to critical loads, such as emergency, substation, lighting, and more. The MFP can house a 42 or 24 circuit panel within it, in addition to UL 98 Mersen low voltage fusible switches as the main fusible disconnect switch and branch fusible disconnect switches. The MFP provides a default short circuit current rating (SCCR) of 200kA under certain conditions and can provide selective coordination using Mersen Amp-Trap 2000® fuses.

    MFP Electrician
  • Mersen Feeder Panel

    MFP is a UL67 listed panelboard that utilizes our commonly available class CC and J fuses. Mersen’s Amp-Trap 2000® class CC and class J fuses ensure minimal fuse let-thru energies and makes it easy to provide system coordination with our easy 2:1 coordination ratios for short circuits.

    • Mersen Panel is UL listed to accept any manufacturer’s Class CC and J fuse
    • Class CC and J fuses are commonly stocked
    • Load connections UL Listed for 2 wires to help with Inspection during last-minute changes
  • Ratings

    Volts

    • 120/208V, 3Ø, 4-wire
    • 120/240V, 1Ø, 3-wire
    • 277/480V, 3Ø, 4-wire
    • 347/600V, 3Ø, 4-wire
    • 125VDC, 2-wire/3-wire

    Amps

    • Main Lug Only Main Bus Ampacity ranges up to 1200A
    • Main Fusible Switch Main Bus Ampacity ranges up to 800A

    Number of Circuits: 

    • Up to 45 circuits

    SCCR

    • 200kA@600V
  • Specifications

    MFP is a patented cULus listed panelboard with an architecture compatible with Mersen UL 98 Fusible Switch and Mersen’s new generation Critical Power Panel (CPP) interior sub-panel, a compact UL67 fused panel rated 250A or 400A with branch circuit protection up to 30A CC.

    DESIGN GUIDE
    Branch Circuit Protection

    • UL Fuse/Circuit Breaker combination
    • Resettable overload protection
    • True class J and CC protection

    Six Branch Fuse Sizes

    • 15A to 30A 4 ATDR30
    • 35A to 60A 4 AJT60
    • 70A to 100A 4 AJT100
    • 125A to 200A 4 AJT200
    • 225A to 400A 4 AJT400
    • 450A to 600A 4 AJT600

    Dimensions

    • 40” wide x 96” high x 17.5” deep

    Main Options

    • Main Lug Only (MLO)
    • Main fusible switch
    • Up to 14 Branch Circuits per Panel

    Main Bus

    • Standard silver-plated copper

    Enclosures

    • NEMA 1, 12, 3R, 4/4X

    Optional Features

    • UL 1449 Listed surge protective devices (required per NEC 700.8)
    • Feed Through Lugs
    • Standard Dual/Sub Feed Lugs on MLO Mains
    • Blown fuse indication (30A, 60A, 100A, 200A, 400A, 600A)
  • Scroll

    Mechanical Characteristics

    cULus Certification         UL67, CSA22.2
    IEC Certification                                          IEC 60529 IP20
    Touchsafe Design  Personnel have no exposure to energized components during operation of the system.

    Electrical Characteristics

    System Ampacity 400A, 600A, 800A, 1200A 
    Main Fusible Switch Ampacity                                400A, 600A, 800A
    Branch Circuit Ampacity 30A, 60A, 100A, 200A, 400A, 600A                                                                                                                     
    Voltage Rating Max. 600VAC & 125VDC
    Withstand (SCCR) 200kA with upstream protection (65kA standalone)
    Neutral 100% or 200% / Linear or Non-linear Loads

    Configurations

    Enclosure UL50 Type 1, 12, 3R, 4/4X
    Main Incoming                                 MLO: (4) #2 to 600 kcmil, Torque: 500 lb.in
    400A MS: (1) #2 - 600 kcmil, Torque: 375 lb.in
    600A/800A MS: (2) #2 - 600 kcmil, Torque: 500 lb.in                          
    Feed-Thru Lug (2) #2 - 600kcmil, Torque: 500 lb.in

     