Back
Where to buy Contact us
PHP-LFBCGT-MSL

NH fuse-links gTr 400VAC, middle indicator/isolated gripping-lugs size 2, 3

Approvals & Standards
VDE 0636 Part 201
IEC 60269-1 and -2

The NH system is classified among plug-in fuse systems and is composed of: * fuse-base, (possibly including terminal covers and phase barriers) * fuse-link with blade contact * fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current, it must be handled by a qualified professional.

NH-fuse links „gTr“ are used for the protection of transformers. The time/current characteristic is especially adapted to that of the protected transformer and implies optimal selectivity to NH-fuse links characteristic gG. The fuses can be loaded with 1,3 times nominal current for up to 10 hours. The fuse link operates at 1,5 times nominal transformer current within 2 hours.

The NH system is classified among plug-in fuse systems and is composed of: * fuse-base, (possibly including terminal covers and phase barriers) * fuse-link with blade contact * fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current, it must be handled by a qualified professional.

NH-fuse links „gTr“ are used for the protection of transformers. The time/current characteristic is especially adapted to that of the protected transformer and implies optimal selectivity to NH-fuse links characteristic gG. The fuses can be loaded with 1,3 times nominal current for up to 10 hours. The fuse link operates at 1,5 times nominal transformer current within 2 hours.

Key features & benefits

  • Maximum transformer capacity (up to 1,3 x In)

  • Reduction of unnecessary interruption of operation

  • Precise cut off of overload

  • Characteristic adapted to the transformer

  • Resistant to ageing

  • Selectivity to fuse links gG

  • High current limiting

  • High breaking capacity

  • Easy selection between transformer and fuse link

Applications

  • Protection of transformers

Technical Specifications
Amperage Range 72 ... 577 A
Speed/Characteristic gTr
CE Conformity Yes
Reach Compliant Yes

Reference Finder

Item number Ampere rating Fuse size Clearing I2t At Rated Voltage Indication System Product weight
T1030532A - NH3GTR75KVA-1 See product
108A NH3 - Yes 1kg
V1030533A - NH3GTR100KVA-1 See product
144A NH3 - Yes 1kg
W1030534A - NH3GTR125KVA-1 See product
180A NH3 - Yes 1kg
X1030535A - NH3GTR160KVA-1 See product
231A NH3 - Yes 1kg
Y1030536A - NH3GTR200KVA-1 See product
289A NH3 - Yes 1kg
Z1030537A - NH3GTR250KVA-1 See product
361A NH3 - Yes 1kg
Back to top