NH fuse-links gTr 400VAC, top indicator/live gripping-lugs size 2, 3, 4a
The NH system is classified among plug-in fuse systems and is composed of: * fuse-base, (possibly including terminal covers and phase barriers) * fuse-link with blade contact * fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current, it must be handled by a qualified professional.
NH-fuse links „gTr“ are used for the protection of transformers. The time/current characteristic is especially adapted to that of the protected transformer and implies optimal selectivity to NH-fuse links characteristic gG. The fuses can be loaded with 1,3 times nominal current for up to 10 hours. The fuse link operates at 1,5 times nominal transformer current within 2 hours.
The NH system is classified among plug-in fuse systems and is composed of: * fuse-base, (possibly including terminal covers and phase barriers) * fuse-link with blade contact * fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current, it must be handled by a qualified professional.
NH-fuse links „gTr“ are used for the protection of transformers. The time/current characteristic is especially adapted to that of the protected transformer and implies optimal selectivity to NH-fuse links characteristic gG. The fuses can be loaded with 1,3 times nominal current for up to 10 hours. The fuse link operates at 1,5 times nominal transformer current within 2 hours.
Product data sheets
- DS-NH-fuse-links-gTr-400VAC-top-indicator-ENpdf - 608.58 KB 
Brochures and Flyers
- DS-NH-Fuse-Handles-ENpdf - 804.83 KB 
Compliance
- COM-REACH-declaration-0019-NHGTR-400V-fusespdf - 368.47 KB 
- COM-CE-ROHS-declaration-0019-NHGTR-400V-fusespdf - 130.75 KB 
- COM-UKCA-declaration-0019-NHGTR-400V-fusespdf - 166.27 KB 
Key features & benefits
- Maximum transformer capacity (up to 1,3 x In) 
- Reduction of unnecessary interruption of operation 
- Precise cut off of overload 
- Characteristic adapted to the transformer 
- Resistant to ageing 
- Selectivity to fuse links gG 
- High current limiting 
- High breaking capacity 
- Easy selection between transformer and fuse link 
Applications
- Protection of transformers 
| Amperage Range | 72 ... 1443 A | 
| Speed/Characteristic | gTr | 
| CE Conformity | 1 | 
| Reach Compliant | Yes | 
Reference Finder
Scroll
| Item number | Ampere rating | Fuse size | Clearing I2t At Rated Voltage | Indication System | Product weight | 
|---|---|---|---|---|---|
| H1028728 - NH4AGTR200KVA-8 See product | 289A | NH4a | - | Yes | 2.2kg | 
| J1028729 - NH4AGTR250KVA-8 See product | 361A | NH4a | - | Yes | 2.2kg | 
| K1028707A - NH3GTR50KVA-8 See product | 72A | NH3 | - | Yes | 1kg | 
| K1028730 - NH4AGTR315KVA-8 See product | 455A | NH4a | - | Yes | 2.2kg | 
| K1030110A - NH32GTR50KVA-8 See product | 72A | NH3 | - | Yes | 1kg | 
| L1028708A - NH3GTR75KVA-8 See product | 108A | NH3 | - | Yes | 1kg | 
| L1028731 - NH4AGTR400KVA-8 See product | 577A | NH4a | - | Yes | 2.2kg | 
| L1030111A - NH32GTR63KVA-8 See product | 63A | NH3 | - | Yes | 1kg | 
| M1028709A - NH3GTR100KVA-8 See product | 144A | NH3 | - | Yes | 1kg | 
| M1030112A - NH32GTR100KVA-8 See product | 144A | NH3 | - | Yes | 1kg | 