Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors.
Back-Up R-Rated Medium Voltage Fuse 4800VAC 5R Mounting: Ferrule Style: Hookeye Visual Indicator Amp-Trap®
Back-Up R-Rated Medium Voltage Fuse 4800VAC 6R Mounting: Ferrule Visual Indicator Amp-Trap®
Back-Up R-Rated Medium Voltage Fuse 4800VAC 6R Mounting: Ferrule Style: Hookeye Visual Indicator Amp-Trap®
Back-Up R-Rated Medium Voltage Fuse 4800VAC 9R Mounting: Ferrule Visual Indicator Amp-Trap®
Back-Up R-Rated Medium Voltage Fuse 4800VAC 9R Mounting: Ferrule Style: Hookeye Visual Indicator Amp-Trap®
DEFINITIONS:
*R-Rating: R-Rated fuses are back-up fuses that operate as follows (Per ANSI C37.46-2000): An R-Rated fuse will melt in the range of 15 to 35 seconds at a value of current equal to 100 times the “R” rating
*Back-up Current-Limiting Fuses: A back-up current-limiting fuse is a fuse that can interrupt any current between its rated minimum interrupting current and its maximum interrupting current. Back-up fuses are not designed or intended to open under overload conditions
*Continuous Ampere Rating at 40°C: The continuous amp rating defines the thermal capability of the fuse per ANSI C37.46 and should not be the sole factor in fuse selection
*Spring-Reinforced Clip MR45 & Spring Ref.# L096472
*Fuse-Holder: SI 24/442 Ref # K209424 In compliance with IEC 282-1, DIN standard 43625
*Note: Ratings above 19R may be achieved by paralleling fuses. Please consult factory for details
Back-Up R-Rated Medium Voltage Fuse 5.5 kV DIN Mount Motor 12R Visual Indicator