Back
Where to buy Contact us
PHP-LFBCA5-MSL

NH fuse-links aM 500VAC , double indicator/live gripping-lugs size 000, 00, 0, 1, 2, 3

Approvals & Standards
VDE 0636 Part 201
IEC 60269-1 and -2

The NH system is classified among plug-in fuse systems and is composed of: * fuse-base (possibly including terminal covers and phase barriers) * fuse-link with blade contact * fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current it must be handled by a qualified professional.

Type "aM" NH fuse-links are partial-range breaking capacity fuse-links, used to protect motor circuits as they are strongly current-limiting and have low power losses. They interrupt currents from 6.3 times In up to their maximum breaking capacity and are therefore suited for short-circuit protection only. They must be associated with other switchgear for protection against overloads. These fuse-links can have a rated current equal to the motor's nominal current.

The NH system is classified among plug-in fuse systems and is composed of: * fuse-base (possibly including terminal covers and phase barriers) * fuse-link with blade contact * fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current it must be handled by a qualified professional.

Type "aM" NH fuse-links are partial-range breaking capacity fuse-links, used to protect motor circuits as they are strongly current-limiting and have low power losses. They interrupt currents from 6.3 times In up to their maximum breaking capacity and are therefore suited for short-circuit protection only. They must be associated with other switchgear for protection against overloads. These fuse-links can have a rated current equal to the motor's nominal current.

Key features & benefits

  • Dimensions according to DIN 43 620 parts 1 to 4

  • Non-isolated gripping lugs

  • Double indicator

  • 0% cadmium

Applications

  • aM: Partial purpose, motor circuit protection

Technical Specifications
Amperage Range 2 ... 630 A
Speed/Characteristic aM
CE Conformity Yes
Reach Compliant Yes

Reference Finder

Item number Ampere rating Fuse size Clearing I2t At Rated Voltage Indication System Product weight
A227884 - NH0AM50V200 See product
200A NH0 - Yes 0.26kg
A232507 - NH0AM50V100 See product
100A NH0 - Yes 0.26kg
B232508 - NH0AM50V125 See product
125A NH0 - Yes 0.26kg
C227863 - NH000AM50V80 See product
80A NH000 - Yes 0.13kg
C232509 - NH0AM50V160 See product
160A NH0 - Yes 0.26kg
D232510 - NH1AM50V100 See product
100A NH1 - Yes 0.42kg
E232511 - NH1AM50V125 See product
125A NH1 - Yes 0.42kg
F232512 - NH1AM50V160 See product
160A NH1 - Yes 0.42kg
G232513 - NH1AM50V200 See product
200A NH1 - Yes 0.42kg
H232514 - NH1AM50V224 See product
224A NH1 - Yes 0.42kg
Back to top