Back
Where to buy Contact us
PHP-LFBCS4-MSL

NH fuse-links gG 400VAC , double indicator/isolated gripping-lugs size 000, 00, 1, 2, 3

Approvals & Standards
VDE 0636 Part 201
IEC 60269-1 and -2

The NH system is classified among plug-in fuse systems and is composed of: * fuse-base (possibly including terminal covers and phase barriers) * fuse-link with blade contact * fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current it must be handled by a qualified professional.

Type "gG" NH fuse-links are full range breaking capacity fuse-links and are used to protect cables and equipment. They can interrupt any current surge, from the lowest fusing current up to their breaking capacity, and so can be used alone as protection. They also protect electrical devices and industrial set-ups from the electrodynamic effects of very high short-circuit currents.

Rated Power Dissipation values of Mersen NH fuse-links 400VAC are below the maximum values required by standard IEC 60269.

The NH system is classified among plug-in fuse systems and is composed of: * fuse-base (possibly including terminal covers and phase barriers) * fuse-link with blade contact * fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current it must be handled by a qualified professional.

Type "gG" NH fuse-links are full range breaking capacity fuse-links and are used to protect cables and equipment. They can interrupt any current surge, from the lowest fusing current up to their breaking capacity, and so can be used alone as protection. They also protect electrical devices and industrial set-ups from the electrodynamic effects of very high short-circuit currents.

Rated Power Dissipation values of Mersen NH fuse-links 400VAC are below the maximum values required by standard IEC 60269.

Key features & benefits

  • Dimensions according to DIN 43 620 Parts 1 to 4

  • Isolated metal gripping lugs (SGL)

  • Double indicator

  • Lead free contact blades

  • 0% cadmium

Applications

  • gG: general purpose cable and line protection

Technical Specifications
Amperage Range 2 ... 630 A
Speed/Characteristic gG
CE Conformity Yes
Reach Compliant Yes

Reference Finder

Item number Ampere rating Fuse size Clearing I2t At Rated Voltage Indication System Product weight
K223753 - NH3GG40V400-1 See product
400A NH3 - Yes 0.65kg
L223754 - NH3GG40V500-1 See product
500A NH3 - Yes 1.05kg
L227250 - NH2GG40V35-1 See product
35A NH2 - Yes 0.4233kg
M223755 - NH3GG40V630-1 See product
630A NH3 - Yes 1.05kg
M227251 - NH2GG40V50-1 See product
50A NH2 - Yes 0.4233kg
N227252 - NH2GG40V63-1 See product
63A NH2 - Yes 0.4233kg
P223688 - NH000GG40V2-1 See product
2A NH000 - Yes 0.1225kg
Q223689 - NH000GG40V4-1 See product
4A NH000 - Yes 0.1225kg
R223690 - NH000GG40V6-1 See product
6A NH000 - Yes 0.1225kg
S223691 - NH000GG40V10-1 See product
10A NH000 - Yes 0.1225kg
Back to top