PHP-LFBCS4-MSL

NH fuse-links gG 400VAC , double indicator/isolated gripping-lugs size 000, 00, 1, 2, 3

Approvals & Standards
VDE 0636 Part 201
IEC 60269-1 and -2

The NH system is classified among plug-in fuse systems and is composed of: * fuse-base (possibly including terminal covers and phase barriers) * fuse-link with blade contact * fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current it must be handled by a qualified professional.

Type "gG" NH fuse-links are full range breaking capacity fuse-links and are used to protect cables and equipment. They can interrupt any current surge, from the lowest fusing current up to their breaking capacity, and so can be used alone as protection. They also protect electrical devices and industrial set-ups from the electrodynamic effects of very high short-circuit currents.

Rated Power Dissipation values of Mersen NH fuse-links 400VAC are below the maximum values required by standard IEC 60269.

The NH system is classified among plug-in fuse systems and is composed of: * fuse-base (possibly including terminal covers and phase barriers) * fuse-link with blade contact * fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current it must be handled by a qualified professional.

Type "gG" NH fuse-links are full range breaking capacity fuse-links and are used to protect cables and equipment. They can interrupt any current surge, from the lowest fusing current up to their breaking capacity, and so can be used alone as protection. They also protect electrical devices and industrial set-ups from the electrodynamic effects of very high short-circuit currents.

Rated Power Dissipation values of Mersen NH fuse-links 400VAC are below the maximum values required by standard IEC 60269.

Key features & benefits

  • Dimensions according to DIN 43 620 Parts 1 to 4

  • Isolated metal gripping lugs (SGL)

  • Double indicator

  • Lead free contact blades

  • 0% cadmium

Applications

  • gG: general purpose cable and line protection

Technical Specifications
Amperage Range 2 ... 630 A
Speed/Characteristic gG
CE Conformity Yes
Reach Compliant Yes

Reference Finder

Item number Ampere rating Fuse size Clearing I2t At Rated Voltage Indication System Product weight
D223724 - NH1GG40V224-1 See product
224A NH1 - Yes 0.4166kg
D223747 - NH2GG40V250-1 See product
250A NH2 - Yes 0.4233kg
E223725 - NH1GG40V250-1 See product
250A NH1 - Yes 0.4166kg
E223748 - NH2GG40V315-1 See product
315A NH2 - Yes 0.6433kg
F223749 - NH2GG40V355-1 See product
355A NH2 - Yes 0.6433kg
G223704 - NH00GG40V125-1 See product
125A NH00 - Yes 0.2kg
G223750 - NH2GG40V400-1 See product
400A NH2 - Yes 0.6433kg
H223705 - NH00GG40V160-1 See product
160A NH00 - Yes 0.2kg
H223751 - NH3GG40V250-1 See product
250A NH3 - Yes 0.65kg
J223752 - NH3GG40V315-1 See product
315A NH3 - Yes 0.65kg
Back to top